Quiz-summary
0 of 30 questions completed
Questions:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
Information
HKIA – Paper 5 – Building Material and Technology
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading...
You must sign in or sign up to start the quiz.
You have to finish following quiz, to start this quiz:
Results
0 of 30 questions answered correctly
Your time:
Time has elapsed
You have reached 0 of 0 points, (0)
Categories
- Not categorized 0%
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- Answered
- Review
-
Question 1 of 30
1. Question
Insulation shall be mechanically retained by
Correct
Insulation shall be mechanically retained by aluminium or galvanized steel clips or straps, or integral pockets within the window frames (General for Building 2017 Edition – Section 16 – Curtain Walls – Thermal Insulation and Fire-Safing Insulation – 16.22).
Incorrect
Insulation shall be mechanically retained by aluminium or galvanized steel clips or straps, or integral pockets within the window frames (General for Building 2017 Edition – Section 16 – Curtain Walls – Thermal Insulation and Fire-Safing Insulation – 16.22).
-
Question 2 of 30
2. Question
Where heat treating results in essentially parallel ripples or waves, the maximum peak-to-valley deviation shall not exceed
Correct
In addition to conforming to BS 952-1, BS 952-2 and ASTM C1048, monolithic heat strengthened and tempered glass shall conform to the following flatness tolerances:
Where heat treating results in essentially parallel ripples or waves, the maximum peak-to-valley deviation shall not exceed 0.127 mm.
Requirements for localized bow and overall bow shall also be satisfied. The direction of ripples shall be consistent throughout the building and approved by the SO.
vii. The specified bow and ripple tolerances are intended as manufacturing quality control limits (General for Building 2017 Edition – Section 20 – Glazing – Flatness – 20.01.04).Incorrect
In addition to conforming to BS 952-1, BS 952-2 and ASTM C1048, monolithic heat strengthened and tempered glass shall conform to the following flatness tolerances:
Where heat treating results in essentially parallel ripples or waves, the maximum peak-to-valley deviation shall not exceed 0.127 mm.
Requirements for localized bow and overall bow shall also be satisfied. The direction of ripples shall be consistent throughout the building and approved by the SO.
vii. The specified bow and ripple tolerances are intended as manufacturing quality control limits (General for Building 2017 Edition – Section 20 – Glazing – Flatness – 20.01.04). -
Question 3 of 30
3. Question
The following types of anchors shall be acceptable:
Correct
The following types of anchors shall not be acceptable:
a. Wires.
b. Anchors whose only means of attachment to stone or building is a bed of grout, mortar, or adhesive.
c. Anchors secured in a hole with lead wool packing.
d. Anchors which transfer load from one piece of stone to another, rather than to the building structure (General for Building 2017 Edition – Section 16 – Curtain Walls – Anchors in Stone – 16.15).Incorrect
The following types of anchors shall not be acceptable:
a. Wires.
b. Anchors whose only means of attachment to stone or building is a bed of grout, mortar, or adhesive.
c. Anchors secured in a hole with lead wool packing.
d. Anchors which transfer load from one piece of stone to another, rather than to the building structure (General for Building 2017 Edition – Section 16 – Curtain Walls – Anchors in Stone – 16.15). -
Question 4 of 30
4. Question
Which of the following is not true about Secondary seal?
Correct
The minimum width of primary seal shall be 3.0 mm. Secondary seal shall be a 2 part neutral cure structural sealant. Secondary seal shall completely cover spacer with no gaps or voids, and shall be continuously bonded to both plates of glass (General for Building 2017 Edition – Section 20 – Glazing – Insulating Glass – 20.01.03).
Incorrect
The minimum width of primary seal shall be 3.0 mm. Secondary seal shall be a 2 part neutral cure structural sealant. Secondary seal shall completely cover spacer with no gaps or voids, and shall be continuously bonded to both plates of glass (General for Building 2017 Edition – Section 20 – Glazing – Insulating Glass – 20.01.03).
-
Question 5 of 30
5. Question
Carpet shall be manufactured by one of the following methods except
Correct
Carpet shall be manufactured by one of the following methods:
i. Single or face-to-face traditional loom.
ii. Needle insertion loom.
iii. Needle punch, fibre bonded, flocked, or knitted.
iv. Other weaving machinery producing the quality of carpet to meet the performance requirements detailed in this specification (General for Building 2017 Edition – Section 18 – Finishes – Classification – 18.143).Incorrect
Carpet shall be manufactured by one of the following methods:
i. Single or face-to-face traditional loom.
ii. Needle insertion loom.
iii. Needle punch, fibre bonded, flocked, or knitted.
iv. Other weaving machinery producing the quality of carpet to meet the performance requirements detailed in this specification (General for Building 2017 Edition – Section 18 – Finishes – Classification – 18.143). -
Question 6 of 30
6. Question
The flakiness index when determined to CS3 shall not exceed 35 for sizes of
Correct
The flakiness index when determined to CS3 shall not exceed 40 for aggregate of 40 mm size or larger, or 35 for sizes of 10 to 28 mm (General for Building 2017 Edition – Section 6 – Structural Concrete Work – Aggregates – 6.33).
Incorrect
The flakiness index when determined to CS3 shall not exceed 40 for aggregate of 40 mm size or larger, or 35 for sizes of 10 to 28 mm (General for Building 2017 Edition – Section 6 – Structural Concrete Work – Aggregates – 6.33).
-
Question 7 of 30
7. Question
Finishes to aluminium alloy shall be as follows except
Correct
Finishes to aluminium alloy shall be as follows:
a. Mill.
b. Polished.
c. Polished and treated with a protective lacquer.
d. Clear anodised shall be to AAMA 611 and of the thickness grade and surface texture as follows:
i. Interior work Class 15 (minimum average thickness of 15µm).
ii. Exterior work Class 25 (minimum average thickness of 25µm).
iii. Internal concealed surface Class 10 (minimum average thickness of 10µm).
e. Colour anodised shall be to AAMA 611 average 25 µm thick.
f. Approved proprietary hardcoat anodic finish with better wearing qualities than standard anodising of the required thickness (General for Building 2017 Edition – Section 17 – Metalwork – Finishes to Aluminium – 17.22).Incorrect
Finishes to aluminium alloy shall be as follows:
a. Mill.
b. Polished.
c. Polished and treated with a protective lacquer.
d. Clear anodised shall be to AAMA 611 and of the thickness grade and surface texture as follows:
i. Interior work Class 15 (minimum average thickness of 15µm).
ii. Exterior work Class 25 (minimum average thickness of 25µm).
iii. Internal concealed surface Class 10 (minimum average thickness of 10µm).
e. Colour anodised shall be to AAMA 611 average 25 µm thick.
f. Approved proprietary hardcoat anodic finish with better wearing qualities than standard anodising of the required thickness (General for Building 2017 Edition – Section 17 – Metalwork – Finishes to Aluminium – 17.22). -
Question 8 of 30
8. Question
In manufactured soil conditioner, Kjeldahl Method is used to test for
Correct
Nitrogen content: (“Kjeldahl” Method) (General for Building 2017 Edition – Section 25 – Landscape Work – Test for manufactured soil conditioner – 25.02).
Incorrect
Nitrogen content: (“Kjeldahl” Method) (General for Building 2017 Edition – Section 25 – Landscape Work – Test for manufactured soil conditioner – 25.02).
-
Question 9 of 30
9. Question
Lightweight aggregate when compacted shall be weighing a maximum of
Correct
Lightweight aggregate shall be clean clinker, or equal and approved, 20-50 mm in diameter, weighing a maximum of 500 kg/m3 when compacted (General for Building 2017 Edition – Section 25 – Landscape Work – Drainage aggregate – 25.11).
Incorrect
Lightweight aggregate shall be clean clinker, or equal and approved, 20-50 mm in diameter, weighing a maximum of 500 kg/m3 when compacted (General for Building 2017 Edition – Section 25 – Landscape Work – Drainage aggregate – 25.11).
-
Question 10 of 30
10. Question
A pile group reduction factor of 0.85 shall be applied to the calculated allowable load capacity of piles unless:
i. The allowable load capacity of the piles is derived from end-bearing
ii. The piles are rock-socketed piles
iii. The centre-to-centre spacings are of more than 1.25 times the perimeter of the piles or the circumscribed rectangles in the case of H-pilesCorrect
A pile group reduction factor of 0.85 shall be applied to the calculated allowable load capacity of piles unless:
i. The centre-to-centre spacings are of more than 3 times the perimeter of the piles or the circumscribed rectangles in the case of H-piles
ii. The allowable load capacity of the piles is derived from end-bearing
iii. The piles are rock-socketed piles
iv. The piles are driven to refusal to rest on rock with final penetration not more than 1.0mm per blow (General for Building 2017 Edition – Section 5 – Piling Work – Pile Group Reduction Factor – 5.07).Incorrect
A pile group reduction factor of 0.85 shall be applied to the calculated allowable load capacity of piles unless:
i. The centre-to-centre spacings are of more than 3 times the perimeter of the piles or the circumscribed rectangles in the case of H-piles
ii. The allowable load capacity of the piles is derived from end-bearing
iii. The piles are rock-socketed piles
iv. The piles are driven to refusal to rest on rock with final penetration not more than 1.0mm per blow (General for Building 2017 Edition – Section 5 – Piling Work – Pile Group Reduction Factor – 5.07). -
Question 11 of 30
11. Question
The concrete produced by the projection of a wetted aggregate/cement mixture onto an area by means of air pressure applied through a continuously feeding pressure vessel is referred to as
Correct
The term “sprayed concrete” refers to the concrete produced by the projection of a wetted aggregate/cement mixture onto an area by means of air pressure applied through a continuously feeding pressure vessel (General for Building 2017 Edition – Section 26 – Geotechnical Works on Soil and Rock Slopes – Glossary of Terms – 26.12).
Incorrect
The term “sprayed concrete” refers to the concrete produced by the projection of a wetted aggregate/cement mixture onto an area by means of air pressure applied through a continuously feeding pressure vessel (General for Building 2017 Edition – Section 26 – Geotechnical Works on Soil and Rock Slopes – Glossary of Terms – 26.12).
-
Question 12 of 30
12. Question
For mechanical rooms, plant rooms, areas subject to vibration, or specified areas, the cohesion/adhesion of the sprayed material shall have a minimum
Correct
Dry density and cohesion/adhesion properties of sprayed material;
For mechanical rooms, plant rooms, areas subject to vibration, or specified areas:
Dry density of the sprayed material shall not be less than 640 kg/m3
The cohesion/adhesion of the sprayed material shall have a minimum 0.35 MPa onto primed steelwork under site tests in accordance with ASTM E736 (General for Building 2017 Edition – Section 15 – Structural Steel Work – Sprayed Mineral Coating – 15.69).Incorrect
Dry density and cohesion/adhesion properties of sprayed material;
For mechanical rooms, plant rooms, areas subject to vibration, or specified areas:
Dry density of the sprayed material shall not be less than 640 kg/m3
The cohesion/adhesion of the sprayed material shall have a minimum 0.35 MPa onto primed steelwork under site tests in accordance with ASTM E736 (General for Building 2017 Edition – Section 15 – Structural Steel Work – Sprayed Mineral Coating – 15.69). -
Question 13 of 30
13. Question
Reinforcement for joints in plasterboard shall be jute scrim cloth not less than
Correct
Reinforcement for joints in plasterboard shall be jute scrim cloth not less than 90 mm wide (General for Building 2017 Edition – Section 18 – Finishes – Joint Reinforcement – 18.33).
Incorrect
Reinforcement for joints in plasterboard shall be jute scrim cloth not less than 90 mm wide (General for Building 2017 Edition – Section 18 – Finishes – Joint Reinforcement – 18.33).
-
Question 14 of 30
14. Question
To be defined as Fully Tempered glass, the residual surface compression must be a minimum of
Correct
To be defined as Fully Tempered glass, the residual surface compression must be a minimum of 69 MPa, however, it is recommended that the glass supplied as fully tempered has a minimum of 75 MPa (General for Building 2017 Edition – Section 20 – Glazing – Fully Tempered Glass – 20.08).
Incorrect
To be defined as Fully Tempered glass, the residual surface compression must be a minimum of 69 MPa, however, it is recommended that the glass supplied as fully tempered has a minimum of 75 MPa (General for Building 2017 Edition – Section 20 – Glazing – Fully Tempered Glass – 20.08).
-
Question 15 of 30
15. Question
For insulation, the conductivity shall not be more than
Correct
For insulation, the conductivity shall not be more than 0.036 w/m deg. C at 24ºC (General for Building 2017 Edition – Section 18 – Finishes – Insulation of Under Cavity Floor where Required – 18.146).
Incorrect
For insulation, the conductivity shall not be more than 0.036 w/m deg. C at 24ºC (General for Building 2017 Edition – Section 18 – Finishes – Insulation of Under Cavity Floor where Required – 18.146).
-
Question 16 of 30
16. Question
Insulate spandrel glass and other non-vision areas with thermal insulation having a
Correct
Insulate spandrel glass and other non-vision areas with thermal insulation having a 50 mm minimum thickness and a 0.127 mm thick reinforced aluminium foil vapour barrier (General for Building 2017 Edition – Section 16 – Curtain Walls – Thermal Insulation and Fire-Safing Insulation – 16.22).
Incorrect
Insulate spandrel glass and other non-vision areas with thermal insulation having a 50 mm minimum thickness and a 0.127 mm thick reinforced aluminium foil vapour barrier (General for Building 2017 Edition – Section 16 – Curtain Walls – Thermal Insulation and Fire-Safing Insulation – 16.22).
-
Question 17 of 30
17. Question
Limestone shall be ground limestone,
Correct
Limestone may be used to reduce the acidity of the soil. It shall be ground limestone, containing a minimum of 90% calcium and magnesium carbonates and capable of passing through a 10 mm mesh sieve (General for Building 2017 Edition – Section 25 – Landscape Work – Limestone – 25.19).
Incorrect
Limestone may be used to reduce the acidity of the soil. It shall be ground limestone, containing a minimum of 90% calcium and magnesium carbonates and capable of passing through a 10 mm mesh sieve (General for Building 2017 Edition – Section 25 – Landscape Work – Limestone – 25.19).
-
Question 18 of 30
18. Question
Lightweight aggregate screeds shall consist of
Correct
Lightweight aggregate screeds shall consist of cement and lightweight aggregate 1:8 for roofs and 1:6 for floors unless contrary to the manufacturers’ recommendations.
Air entrained screeds shall have a dry density of not more than 1,200 kg/m3 (General for Building 2017 Edition – Section 18 – Finishes – Lightweight Screeds – 18.80)Incorrect
Lightweight aggregate screeds shall consist of cement and lightweight aggregate 1:8 for roofs and 1:6 for floors unless contrary to the manufacturers’ recommendations.
Air entrained screeds shall have a dry density of not more than 1,200 kg/m3 (General for Building 2017 Edition – Section 18 – Finishes – Lightweight Screeds – 18.80) -
Question 19 of 30
19. Question
Supply concrete in sufficient quantities to ensure that concreting of each pile proceeds without interruption, the concrete shall have minimum slump of
Correct
Supply concrete in sufficient quantities to ensure that concreting of each pile proceeds without interruption. The concrete shall have a minimum cement content of 400 kg/m3 and a minimum slump of 150 mm (General for Building 2017 Edition – Section 5 – Piling Work – Large Diameter Bored Piles – 5.19).
Incorrect
Supply concrete in sufficient quantities to ensure that concreting of each pile proceeds without interruption. The concrete shall have a minimum cement content of 400 kg/m3 and a minimum slump of 150 mm (General for Building 2017 Edition – Section 5 – Piling Work – Large Diameter Bored Piles – 5.19).
-
Question 20 of 30
20. Question
Fabricated Soil Mix shall consist of friable, completely decomposed granite (or volcanic) and manufactured soil conditioner in the proportions of
Correct
Fabricated Soil Mix shall consist of friable, completely decomposed granite (or volcanic) and manufactured soil conditioner in the proportions of 3:1 by volume (General for Building 2017 Edition – Section 25 – Landscape Work – Fabricated Soil Mix – 25.02).
Incorrect
Fabricated Soil Mix shall consist of friable, completely decomposed granite (or volcanic) and manufactured soil conditioner in the proportions of 3:1 by volume (General for Building 2017 Edition – Section 25 – Landscape Work – Fabricated Soil Mix – 25.02).
-
Question 21 of 30
21. Question
Non-slip strip insert shall be
i. 25 x 15 mm slightly curved on top
ii. consist of a proprietary insert strip
iii. consist of a compound of cement and carborundum dust 1:2Correct
Non-slip strip insert shall be 25 x 15 mm slightly curved on top and consisting of:
i. A compound of cement and carborundum dust 1:1, or
ii. A proprietary insert strip.
(General for Building 2017 Edition – Section 18 – Finishes – Non-Slip Strip – 18.88)Incorrect
Non-slip strip insert shall be 25 x 15 mm slightly curved on top and consisting of:
i. A compound of cement and carborundum dust 1:1, or
ii. A proprietary insert strip.
(General for Building 2017 Edition – Section 18 – Finishes – Non-Slip Strip – 18.88) -
Question 22 of 30
22. Question
Which of the following statement is correct? Unless otherwise state; Top bolts to doors up to 2000mm high shall be 150mm long
For taller doors,Correct
Unless otherwise stated:
a. Bottom bolts shall be 150mm minimum long.
b. Top bolts to doors up to 2000mm high shall be 150mm long. For taller doors, increase bolt length by 150mm for each 150mm of additional height, or part thereof. For very tall doors, automatic flush bolts may be substituted (General for Building 2017 Edition – Section 14 – Ironmongery – Bolts – 14.88).Incorrect
Unless otherwise stated:
a. Bottom bolts shall be 150mm minimum long.
b. Top bolts to doors up to 2000mm high shall be 150mm long. For taller doors, increase bolt length by 150mm for each 150mm of additional height, or part thereof. For very tall doors, automatic flush bolts may be substituted (General for Building 2017 Edition – Section 14 – Ironmongery – Bolts – 14.88). -
Question 23 of 30
23. Question
Which of the following statement is true?
Correct
Unless specifically designed to clear an obstruction at the point of installation, the length of the bottom rail including end-caps shall be within ±3 mm of the overall width of the blind (General for Building 2017 Edition – Section 22 – Internal Fittings and Fixtures – Bottom rail – 22.45).
Incorrect
Unless specifically designed to clear an obstruction at the point of installation, the length of the bottom rail including end-caps shall be within ±3 mm of the overall width of the blind (General for Building 2017 Edition – Section 22 – Internal Fittings and Fixtures – Bottom rail – 22.45).
-
Question 24 of 30
24. Question
The minimum service life of all gaskets, weather stripping, and other glazing accessories shall be
Correct
The minimum service life of all gaskets, weather stripping, and other glazing accessories shall be 15 years (General for Building 2017 Edition – Section 20 – Glazing – Glazing Materials – 20.01.04).
Incorrect
The minimum service life of all gaskets, weather stripping, and other glazing accessories shall be 15 years (General for Building 2017 Edition – Section 20 – Glazing – Glazing Materials – 20.01.04).
-
Question 25 of 30
25. Question
Which of the following statement is not true about cement-based plaster?
Correct
Cement-based plaster contains mineral filler material as aggregate and portland cement as main binder, with additives for improved compressive strength and reduced shrinkage
Gypsum based plaster contains pre-mixed minerals, gypsum base rendering materials, and additives which could be applied in one single thick application without cracking and separation from the substrate (General for Building 2017 Edition – Section 18 – Finishes – Cement Based Premixed Plaster – 18.58).Incorrect
Cement-based plaster contains mineral filler material as aggregate and portland cement as main binder, with additives for improved compressive strength and reduced shrinkage
Gypsum based plaster contains pre-mixed minerals, gypsum base rendering materials, and additives which could be applied in one single thick application without cracking and separation from the substrate (General for Building 2017 Edition – Section 18 – Finishes – Cement Based Premixed Plaster – 18.58). -
Question 26 of 30
26. Question
Structural sealant shall be the following except
Correct
Structural sealant shall be either:
a. One part gun grade neutral moisture curing silicone elastomeric sealant or
b. Two part structural silicone elastomeric sealant. Products requiring mixing of components shall be acceptable only for shop application with mixing and application equipment acceptable to the sealant manufacturer (General for Building 2017 Edition – Section 16 – Curtain Walls – Sealants – 16.21).Incorrect
Structural sealant shall be either:
a. One part gun grade neutral moisture curing silicone elastomeric sealant or
b. Two part structural silicone elastomeric sealant. Products requiring mixing of components shall be acceptable only for shop application with mixing and application equipment acceptable to the sealant manufacturer (General for Building 2017 Edition – Section 16 – Curtain Walls – Sealants – 16.21). -
Question 27 of 30
27. Question
For grout having minimum cube strength of 30 MPa at 28 days, design bond strength between bedrock and grout shall not exceed
Correct
Design bond strength between bedrock and grout shall not exceed 0.7 MPa for grout having minimum cube strength of 30 MPa at 28 days and 0.64 MPa for grout having minimum cube strength of 25 MPa at 28 days (General for Building 2017 Edition – Section 5 – Piling Work – Minipiles – 5.21).
Incorrect
Design bond strength between bedrock and grout shall not exceed 0.7 MPa for grout having minimum cube strength of 30 MPa at 28 days and 0.64 MPa for grout having minimum cube strength of 25 MPa at 28 days (General for Building 2017 Edition – Section 5 – Piling Work – Minipiles – 5.21).
-
Question 28 of 30
28. Question
Provide mechanical retention for the sprayed mineral coating by means of mesh reinforcement unless
Correct
Provide mechanical retention for the sprayed mineral coating by means of mesh reinforcement in accordance with BS 8202-1 unless:
a. There is evidence from fire resistance tests to show that there is adequate bond between the spray and the substrate (including primers or other coatings)
b. The spray is locked in position by virtue of the shape of the element (General for Building 2017 Edition – Section 15 – Structural Steel Work – Sprayed Mineral Coating – 15.69).Incorrect
Provide mechanical retention for the sprayed mineral coating by means of mesh reinforcement in accordance with BS 8202-1 unless:
a. There is evidence from fire resistance tests to show that there is adequate bond between the spray and the substrate (including primers or other coatings)
b. The spray is locked in position by virtue of the shape of the element (General for Building 2017 Edition – Section 15 – Structural Steel Work – Sprayed Mineral Coating – 15.69). -
Question 29 of 30
29. Question
Roller shutters shall be either:
i. Mechanically operated by an endless chain
ii. Electrically operated
iii. Self – closingCorrect
Roller shutters shall be either:
i. Self – closing.
ii. Manually operated by an endless chain.
iii. Electrically operated (General for Building 2017 Edition – Section 17 – Metalwork – Roller Shutters and Doors – 17.41).Incorrect
Roller shutters shall be either:
i. Self – closing.
ii. Manually operated by an endless chain.
iii. Electrically operated (General for Building 2017 Edition – Section 17 – Metalwork – Roller Shutters and Doors – 17.41). -
Question 30 of 30
30. Question
Minimum width of primary seal shall be
Correct
Minimum width of primary seal shall be 3.0 mm. Secondary seal shall be a 2 part neutral cure structural sealant. Secondary seal shall completely cover spacer with no gaps or voids, and shall be continuously bonded to both plates of glass (General for Building 2017 Edition – Section 20 – Glazing – Insulating Glass – 20.01.03).
Incorrect
Minimum width of primary seal shall be 3.0 mm. Secondary seal shall be a 2 part neutral cure structural sealant. Secondary seal shall completely cover spacer with no gaps or voids, and shall be continuously bonded to both plates of glass (General for Building 2017 Edition – Section 20 – Glazing – Insulating Glass – 20.01.03).