Quiz-summary
0 of 30 questions completed
Questions:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
Information
HKIA – Paper 5 – Building Material and Technology
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading...
You must sign in or sign up to start the quiz.
You have to finish following quiz, to start this quiz:
Results
0 of 30 questions answered correctly
Your time:
Time has elapsed
You have reached 0 of 0 points, (0)
Categories
- Not categorized 0%
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- Answered
- Review
-
Question 1 of 30
1. Question
The difference between Dead load and Imposed load is
Correct
Dead load means the weight of walls, floors, roofs, finishes, permanent partitions, and other permanent construction.
Imposed load means load other than dead load or wind load;
Wind load means any load due to the effects of wind pressure or suction
(Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part I – General – 2 – Interpretation).Incorrect
Dead load means the weight of walls, floors, roofs, finishes, permanent partitions, and other permanent construction.
Imposed load means load other than dead load or wind load;
Wind load means any load due to the effects of wind pressure or suction
(Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part I – General – 2 – Interpretation). -
Question 2 of 30
2. Question
Every refuse chute shall
Correct
Every refuse chute shall
a. be lined with glazed ware or other impervious tubes
b. have an internal diameter of not less than 450 mm
(Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 16).Incorrect
Every refuse chute shall
a. be lined with glazed ware or other impervious tubes
b. have an internal diameter of not less than 450 mm
(Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 16). -
Question 3 of 30
3. Question
The channel of a trough water closet shall not be longer than
Correct
The channel of a trough water closet shall not be longer than 5 m and shall have an even fall towards the outlet trap of not less than 1 in 30 (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 15).
Incorrect
The channel of a trough water closet shall not be longer than 5 m and shall have an even fall towards the outlet trap of not less than 1 in 30 (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 15).
-
Question 4 of 30
4. Question
Which of the following statement(s) is/are wrong? Flushing cistern shall in the case of water closet fitments and slop sinks
i. discharge to the water closet fitment of slop sink, on each occasion such fitment is used, not less than 6 litres and not more than 10 litres of water
ii. be provided with a ball valve so arranged as to refill the cistern within 2 minutes
iii. Wrong discharge at the highest point of the channelCorrect
Such flushing cistern shall in the case of water closet fitments and slop sinks
i. discharge to the water closet fitment of slop sink, on each occasion such fitment is used, not less than 9 litres and not more than 14 litres of water; and
ii. be provided with a ball valve so arranged as to refill the cistern within 2 minutes (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 19).Incorrect
Such flushing cistern shall in the case of water closet fitments and slop sinks
i. discharge to the water closet fitment of slop sink, on each occasion such fitment is used, not less than 9 litres and not more than 14 litres of water; and
ii. be provided with a ball valve so arranged as to refill the cistern within 2 minutes (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 19). -
Question 5 of 30
5. Question
Which of the statement is not true about Overflow pipes?
Correct
The overflow pipe from a water storage tank shall
a. have an internal diameter of one commercial size larger than the supply pipe to the cistern or tank
b. dip down, inside the tank, so as to terminate in a position not more than 150 mm above the bottom of the tank
c. discharge in a conspicuous position (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 23).Incorrect
The overflow pipe from a water storage tank shall
a. have an internal diameter of one commercial size larger than the supply pipe to the cistern or tank
b. dip down, inside the tank, so as to terminate in a position not more than 150 mm above the bottom of the tank
c. discharge in a conspicuous position (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 23). -
Question 6 of 30
6. Question
Every waste fitment shall be provided immediately under the fitment with a suitable trap, where the waste pipe from a waste fitment is, connected to a soil pipe, the trap provided for the waste fitment shall
Correct
Every waste fitment shall be provided immediately under the fitment with a suitable trap, where the waste pipe from a waste fitment is, connected to a soil pipe, the trap provided for the waste fitment shall
a. have an internal diameter of not less than 32 mm;
b. have a water seal of not less than 80 mm; and
c. be:
i. adequately ventilated or
ii. constructed to prevent loss of water seal (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 25).Incorrect
Every waste fitment shall be provided immediately under the fitment with a suitable trap, where the waste pipe from a waste fitment is, connected to a soil pipe, the trap provided for the waste fitment shall
a. have an internal diameter of not less than 32 mm;
b. have a water seal of not less than 80 mm; and
c. be:
i. adequately ventilated or
ii. constructed to prevent loss of water seal (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 25). -
Question 7 of 30
7. Question
If the discharge point of the exit route to the ultimate place of safety is so sited that it adjoins another exit route or other accommodation,
Correct
If the discharge point of the exit route to the ultimate place of safety is so sited that it adjoins another exit route or other accommodation, the walls enclosing the exit route should be returned along the frontage of the final discharge or project from the frontage for a distance of not less than 450mm, provided that any return should not reduce the effective width of the exit route (Code of Practice for Fire Safety in Buildings 2011 – Part B – Means of Escape – Section 2 – Provisions of Means of Escape – Subsection B5 – General Requirements of Exit Routes – Clause B5.7).
Incorrect
If the discharge point of the exit route to the ultimate place of safety is so sited that it adjoins another exit route or other accommodation, the walls enclosing the exit route should be returned along the frontage of the final discharge or project from the frontage for a distance of not less than 450mm, provided that any return should not reduce the effective width of the exit route (Code of Practice for Fire Safety in Buildings 2011 – Part B – Means of Escape – Section 2 – Provisions of Means of Escape – Subsection B5 – General Requirements of Exit Routes – Clause B5.7).
-
Question 8 of 30
8. Question
All materials used in any building works or street works shall be;
Correct
All materials used in any building works or street works shall be;
a. of a suitable nature and quality for the purposes for which they are used;
b. adequately mixed or prepared; and
c. applied, used or fixed so as to perform adequately the functions for which they are designed (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part I – General – 3 – Materials).Incorrect
All materials used in any building works or street works shall be;
a. of a suitable nature and quality for the purposes for which they are used;
b. adequately mixed or prepared; and
c. applied, used or fixed so as to perform adequately the functions for which they are designed (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part I – General – 3 – Materials). -
Question 9 of 30
9. Question
A weep hole, with an internal diameter of not less than 50 mm, shall be provided to every
Correct
A weep hole, with an internal diameter of not less than 50 mm, shall be provided to every 1.5 m2 of the face of chunamed surface and in areas of localized seepage (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part II – Materials – 14 – Chunam – 2).
Incorrect
A weep hole, with an internal diameter of not less than 50 mm, shall be provided to every 1.5 m2 of the face of chunamed surface and in areas of localized seepage (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part II – Materials – 14 – Chunam – 2).
-
Question 10 of 30
10. Question
The resistance to the uplift force shall be calculated as
Correct
The resistance to the uplift force shall be calculated as the sum of the downward force due to the minimum dead loads plus that due to any permitted anchoring resistance (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part III – Loads – 15 – Resistance to Sliding, Uplift, and Overturning – 2).
Incorrect
The resistance to the uplift force shall be calculated as the sum of the downward force due to the minimum dead loads plus that due to any permitted anchoring resistance (Building (Construction) Regulations (Cap. 123 sub. leg. B) – Part III – Loads – 15 – Resistance to Sliding, Uplift, and Overturning – 2).
-
Question 11 of 30
11. Question
Every building shall be designed and constructed so as to;
i. inhibit the spread of fire within the building and to nearby buildings by dividing the building into compartments.
ii. provide adequate resistance to the spread of fire and smoke by the separation of different uses in a building by compartment walls and floors and by the separation of the building from any adjoining building or site.
ii. provide adequate resistance to the spread of fire over the roof of one building to another having regard to the position of the building.Correct
Every building shall be designed and constructed so as to-
a. inhibit the spread of fire within the building and to nearby buildings by dividing the building into compartments;
b. provide adequate resistance to the spread of fire and smoke by the separation of different uses in a building by compartment walls and floors and by the separation of the building from any adjoining building or site;
c. maintain the stability of the building in case of fire; and
d. provide adequate resistance to the spread of fire over the roof of one building to another having regard to the position of the building (Code of Practice for Fire Safety in Buildings 2011 – Part A – Introduction – Section 2 – Performance Requirements – Subsection A9 – Fire Resisting Construction)Incorrect
Every building shall be designed and constructed so as to-
a. inhibit the spread of fire within the building and to nearby buildings by dividing the building into compartments;
b. provide adequate resistance to the spread of fire and smoke by the separation of different uses in a building by compartment walls and floors and by the separation of the building from any adjoining building or site;
c. maintain the stability of the building in case of fire; and
d. provide adequate resistance to the spread of fire over the roof of one building to another having regard to the position of the building (Code of Practice for Fire Safety in Buildings 2011 – Part A – Introduction – Section 2 – Performance Requirements – Subsection A9 – Fire Resisting Construction) -
Question 12 of 30
12. Question
Every part of an exit route should have a clear headroom of not less than 2000mm, provided that
Correct
Every part of an exit route should have a clear headroom of not less than 2000mm, provided that sprinkler heads may be installed along the sidewall of the exit route and every such sprinkler head should not project:
a. more than 90mm from such sidewall and
b. so as to reduce the clear headroom of the exit route by more than 105mm (Code of Practice for Fire Safety in Buildings 2011 – Part B – Means of Escape – Section 2 – Provisions of Means of Escape – Subsection B5 – General Requirements of Exit Routes – Clause B5.9).Incorrect
Every part of an exit route should have a clear headroom of not less than 2000mm, provided that sprinkler heads may be installed along the sidewall of the exit route and every such sprinkler head should not project:
a. more than 90mm from such sidewall and
b. so as to reduce the clear headroom of the exit route by more than 105mm (Code of Practice for Fire Safety in Buildings 2011 – Part B – Means of Escape – Section 2 – Provisions of Means of Escape – Subsection B5 – General Requirements of Exit Routes – Clause B5.9). -
Question 13 of 30
13. Question
Fire resistance ratings are designated by three terms, to represent the makeup of the element of construction except
Correct
Fire Resistance Rating (FRR) means the period of time that a building element is capable of resisting the action of fire when tested in accordance with ISO 834, BS 476: Parts 20 to 24 or equivalent. Fire resistance ratings are designated by three terms, to represent the makeup of the element of construction, i.e. X/Y/Z, where:
• X – Stability Fire Resistance Rating (minutes)
• Y – Integrity Fire Resistance Rating (minutes)
• Z – Insulation Fire Resistance Rating (minutes)
(Code of Practice for Fire Safety in Buildings 2011 – Part A – Introduction – Section 3 – Definition).Incorrect
Fire Resistance Rating (FRR) means the period of time that a building element is capable of resisting the action of fire when tested in accordance with ISO 834, BS 476: Parts 20 to 24 or equivalent. Fire resistance ratings are designated by three terms, to represent the makeup of the element of construction, i.e. X/Y/Z, where:
• X – Stability Fire Resistance Rating (minutes)
• Y – Integrity Fire Resistance Rating (minutes)
• Z – Insulation Fire Resistance Rating (minutes)
(Code of Practice for Fire Safety in Buildings 2011 – Part A – Introduction – Section 3 – Definition). -
Question 14 of 30
14. Question
No refuse storage and material recovery chamber shall have any dimension less than
Correct
No refuse storage and material recovery chamber shall have any dimension less than 1.5 m (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 8 – Minimum Dimensions of Refuse Storage and Material Recovery Chambers – 1)
Incorrect
No refuse storage and material recovery chamber shall have any dimension less than 1.5 m (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 8 – Minimum Dimensions of Refuse Storage and Material Recovery Chambers – 1)
-
Question 15 of 30
15. Question
Which of the following statement is true about the construction of hopper?
Correct
The inner plate of every hopper shall project downward at an angle of not less than 45 degrees to the horizontal when the hopper is closed (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 23 – Construction of Hopper – 5).
Incorrect
The inner plate of every hopper shall project downward at an angle of not less than 45 degrees to the horizontal when the hopper is closed (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 23 – Construction of Hopper – 5).
-
Question 16 of 30
16. Question
Open Air means a space which
i. is vertically uncovered and unobstructed
ii. is not less, in any vertical, than 1.3m
iii. where such space is enclosed on 4 sides, has a horizontal area of not less than 1 m2 for every 6 m of the mean height of the walls enclosing the spaceCorrect
Open Air means a space which
a. is vertically uncovered and unobstructed;
b. is not less, in any horizontal dimension, than 1.5 m; and
c. where such space is enclosed on 4 sides, has a horizontal area of not less than 1 m2 for every 6 m of the mean height of the walls enclosing the space (Building (Planning) Regulations
(Cap. 123 sub. leg. F) – Part I – General – 2 – Interpretation)Incorrect
Open Air means a space which
a. is vertically uncovered and unobstructed;
b. is not less, in any horizontal dimension, than 1.5 m; and
c. where such space is enclosed on 4 sides, has a horizontal area of not less than 1 m2 for every 6 m of the mean height of the walls enclosing the space (Building (Planning) Regulations
(Cap. 123 sub. leg. F) – Part I – General – 2 – Interpretation) -
Question 17 of 30
17. Question
Which of the following statement is not correct?
The internal diameter of every such trap shall be not less than
i. 70 mm, in the case of a water closet fitment, slop sink, or urinal with more than 3 basins or stalls or with a channel longer than 2 m
ii. 50 mm, in the case of a urinal with more than one and not more than 3 basins or stalls or with a channel not longer than 2 m
iii. 60 mm, in the case of a bidet or urinal with a single basin or stall and
iv. 100 mm, in the case of a trough water closetCorrect
The internal diameter of every such trap shall be not less than
a. 80 mm, in the case of a water closet fitment, slop sink, or urinal with more than 3 basins or stalls or with a channel longer than 2m
b. 50 mm, in the case of a urinal with more than one and not more than 3 basins or stalls or with a channel not longer than 2m
c. 40 mm, in the case of a bidet or urinal with a single basin or stall and
d. 100 mm, in the case of a trough water closet (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 24).Incorrect
The internal diameter of every such trap shall be not less than
a. 80 mm, in the case of a water closet fitment, slop sink, or urinal with more than 3 basins or stalls or with a channel longer than 2m
b. 50 mm, in the case of a urinal with more than one and not more than 3 basins or stalls or with a channel not longer than 2m
c. 40 mm, in the case of a bidet or urinal with a single basin or stall and
d. 100 mm, in the case of a trough water closet (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 24). -
Question 18 of 30
18. Question
The size of eaves gutters shall be calculated at the rate of
Correct
The size of eaves gutters shall be calculated at the rate of 700 mm2 of the cross-sectional area of gutter to every 7 m2 of horizontal roofed-over surface (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 38).
Incorrect
The size of eaves gutters shall be calculated at the rate of 700 mm2 of the cross-sectional area of gutter to every 7 m2 of horizontal roofed-over surface (Buildings (Standards of Sanitary Fitments, Plumbing, Drainage Works and Latrines) Regulations (Cap. 123 sub. leg. I) – Part III – Plumbing – 38).
-
Question 19 of 30
19. Question
The floor of every refuse storage and material recovery chamber shall be
Correct
The floor of every refuse storage and material recovery chamber shall be—
a. constructed of concrete not less than 100 mm thick; (L.N. 439 of 1990)
b. laid to fall towards the gully provided in accordance with regulation 11; and
c. finished with quarry tiles or other approved hard impervious material (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 9 – Construction of Refuse Storage and Material Recovery Chambers – 4)Incorrect
The floor of every refuse storage and material recovery chamber shall be—
a. constructed of concrete not less than 100 mm thick; (L.N. 439 of 1990)
b. laid to fall towards the gully provided in accordance with regulation 11; and
c. finished with quarry tiles or other approved hard impervious material (Building (Refuse Storage and Material Recovery Chambers and Refuse Chutes) Regulations (Cap. 123 sub. leg. H) – 9 – Construction of Refuse Storage and Material Recovery Chambers – 4) -
Question 20 of 30
20. Question
Every opening placed on an external wall above the ground floor of any building shall be protected by a barrier which shall be not less than
Correct
Every opening placed on an external wall above the ground floor of any building shall be protected by a barrier which shall be not less than 1100 mm high and the lowermost 150mm of such barrier shall be built solid (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 3A – Protection of Openings – 1)
Incorrect
Every opening placed on an external wall above the ground floor of any building shall be protected by a barrier which shall be not less than 1100 mm high and the lowermost 150mm of such barrier shall be built solid (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 3A – Protection of Openings – 1)
-
Question 21 of 30
21. Question
Which of the following statement is true about the space about domestic buildings?
Correct
No part of any domestic building shall be erected within 1.5 m of the rear boundary of the site. The open space so provided shall be counted as part of the open space required under this regulation (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 25 – Space about Domestic Buildings – 2).
Incorrect
No part of any domestic building shall be erected within 1.5 m of the rear boundary of the site. The open space so provided shall be counted as part of the open space required under this regulation (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 25 – Space about Domestic Buildings – 2).
-
Question 22 of 30
22. Question
Every room containing a soil fitment or waste fitment shall be provided with a window or lantern light, every such window or lantern light shall be such that the aggregate superficial area of glass therein is not less than
Correct
Every room containing a soil fitment or waste fitment shall be provided with a window or lantern light, every such window or lantern light shall be such that the aggregate superficial area of glass therein is not less than the equivalent of one-tenth of the area of the floor of the room (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 36 – Rooms Containing Soil Fitments – 2).
Incorrect
Every room containing a soil fitment or waste fitment shall be provided with a window or lantern light, every such window or lantern light shall be such that the aggregate superficial area of glass therein is not less than the equivalent of one-tenth of the area of the floor of the room (Building (Planning) Regulations (Cap. 123 sub. leg. F) – 36 – Rooms Containing Soil Fitments – 2).
-
Question 23 of 30
23. Question
The Shading Coefficient of Fenestration is
Correct
The Shading Coefficient of Fenestration is the ratio of the solar heat gain through a particular type of glass under a specific set of conditions to the solar heat gain through double strength sheet clear glass under the same conditions (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – 7 – Calculation of Components Coefficients and Parameter of Overall Thermal Transfer Value (OTTV) – Shading Coefficient of Fenestration (SC) – 7.5)
Incorrect
The Shading Coefficient of Fenestration is the ratio of the solar heat gain through a particular type of glass under a specific set of conditions to the solar heat gain through double strength sheet clear glass under the same conditions (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – 7 – Calculation of Components Coefficients and Parameter of Overall Thermal Transfer Value (OTTV) – Shading Coefficient of Fenestration (SC) – 7.5)
-
Question 24 of 30
24. Question
The absorptivity of black glass is
Correct
The absorptivity of black glass is 1.0 (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – Table 4)
Incorrect
The absorptivity of black glass is 1.0 (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – Table 4)
-
Question 25 of 30
25. Question
The thermal conductivity (k), Watts per Metre Celcius of Asphalt, mastic with 20% grit is
Correct
The thermal conductivity (k), Watts per Metre Celcius of Asphalt, mastic with 20% grit is 1.15 (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – Table 1)
Incorrect
The thermal conductivity (k), Watts per Metre Celcius of Asphalt, mastic with 20% grit is 1.15 (Code of Practice for Overall Thermal Transfer Value in Buildings 1995 – Table 1)
-
Question 26 of 30
26. Question
Safety ropes on scaffolding shall have a breaking force of at least
Correct
Install a system of safety ropes on the scaffolding. Safety ropes shall be 12mm diameter and shall have a breaking force of at least 18 kN (General Specification for Building 2017 Edition – Section 26 – Geotechnical Works on Soil and Rock Slopes – Preparation Works – 26.01)
Incorrect
-
Question 27 of 30
27. Question
The apparatus for measuring deformation shall be capable of measuring a displacement of up to
Correct
The apparatus for measuring deformation shall be capable of measuring a displacement of up to 50mm (General Specification for Building 2017 Edition – Section 26 – Geotechnical Works on Soil and Rock Slopes – Pull-Out Test – 26.39)
Incorrect
The apparatus for measuring deformation shall be capable of measuring a displacement of up to 50mm (General Specification for Building 2017 Edition – Section 26 – Geotechnical Works on Soil and Rock Slopes – Pull-Out Test – 26.39)
-
Question 28 of 30
28. Question
Heavy-duty, modular, security locks shall be obtained from an approved reputable source with
Correct
Heavy-duty, modular, security locks shall be obtained from an approved reputable source with 60mm minimum backset and 72mm centres (General Specification for Building 2017 Edition – Section 14 – Ironmongery – Locks – 14.58)
Incorrect
-
Question 29 of 30
29. Question
Quantity of sand/filler used shall not exceed
Correct
Quantity of sand/filler used shall not exceed 30% of the mass of cement (General Specification for Building 2017 Edition – Section 7 – Prestressed Concontre Works – Mix Proportions of Grouts – 7.07)
Incorrect
Quantity of sand/filler used shall not exceed 30% of the mass of cement (General Specification for Building 2017 Edition – Section 7 – Prestressed Concontre Works – Mix Proportions of Grouts – 7.07)
-
Question 30 of 30
30. Question
Unsuitable material is a material other than suitable material or containing any of the following:
i. Peat, vegetation, timber, organic, soluble or perishable material.
ii. Dangerous or toxic material or material susceptible to combustion.
iii. Metal, rubber, plastic or synthetic materialCorrect
Unsuitable material is a material other than suitable material or containing any of the following:
a. Material susceptible to volume change, including marine mud, soil with a liquid limit exceeding 65% or a plasticity index exceeding 35%, swelling clays, and collapsible soils.
b. Peat, vegetation, timber, organic, soluble or perishable material.
c. Dangerous or toxic material or material susceptible to combustion.
d. Metal, rubber, plastic or synthetic material (General Specification for Building 2017 Edition – Section 3 – Excavation and Earthwork – Definitions – 3.01).Incorrect
Unsuitable material is a material other than suitable material or containing any of the following:
a. Material susceptible to volume change, including marine mud, soil with a liquid limit exceeding 65% or a plasticity index exceeding 35%, swelling clays, and collapsible soils.
b. Peat, vegetation, timber, organic, soluble or perishable material.
c. Dangerous or toxic material or material susceptible to combustion.
d. Metal, rubber, plastic or synthetic material (General Specification for Building 2017 Edition – Section 3 – Excavation and Earthwork – Definitions – 3.01).